Current Rating for Copper Busbar

Sunday, July 31, 2011 · 0 comments

The following table shows current rating for different size of busbar. This information is very crucial especially in designing the busbar size for Electrical Switchboard.

(A) Main Horizontal & Vertical Copper Busbar Size

Item

Busbar Size

Rating (Ampere)

1

1 x 3 mm x 25 mm

100

2

1 x 5 mm x 25 mm

160

3

1 x 6 mm x 25 mm

200

4

1 x 6 mm x 30 mm

250

5

1 x 6 mm x 40 mm

300

6

1 x 10 mm x 30 mm

400

7

1 x 10 mm x 40 mm

500 - 600

8

1 x 10 mm x 50 mm

700

9

1 x 10 mm x 55 mm

800


 

(B) Main Horizontal Earth Busbar Size

Item

Busbar Size

Rating (Ampere)

1

1 x 3 mm x 25 mm

Below 800


 

(C) MCCB Line & Load Cable Size (BS 6004: 1984,450/750 V)

Item

Busbar Size

Rating (Ampere)

1

1 x 2.5 mm

6 – 16

2

1 x 4.0 mm

20

3

1 x 6.0 mm

30 – 32

4

1 x 10 mm

40

5

1 x 16 mm

50 – 63

6

1 x 25 mm

70 – 90

7

1 x 35 mm

100

8

1 x 50 mm

125 – 150

9

1 x 70 mm

175 – 200

10

1 x 95 mm

225 - 250

Requirement on Fireman Switch

Monday, July 18, 2011 · 0 comments
A Fireman’s switch is an electrical isolation switch located within a staircase enclosure to permit the disconnection of electrical power supply to the relevant floor or zone served. In England, it is code that every floor or zone of any floor with a net area exceeding 929 square metres shall be provided with a switch. The switch is of a type similar to the firemen's switch specified in the current edition of Institution of Electrical Engineers Regulations then in force. These switches are most commonly found on retail premises nearby to illuminated neon and LED signage.

What you need to know on Fireman Switch?
  1.  The most important is designer should consult with local authority-fire department on exact requirement before establish design on fireman switch. The requirement may differ between state or country.
  2. Red in Color
  3. The switch should be placed in a conspicuous and accessible location, not more that 2.75m from finish floor level.
  4. The fireman switch should be outside and adjacent to the installation for external installations and i the main entrance of a buildings for interior installations.


Fireman switch shall be clearly labeled as accordance to its purpose/which MSB,DBand Electrical panel to be isolated. Photo below showing how fireman isolate the power supply from fireman switch. One of the manufacturer supply fireman switch is ABB Product.

Capacitor Bank In MSB

Saturday, July 16, 2011 · 1 comments
The purpose of installing the capacitor bank is to counter the resistive load (KVAR) in the electrical system. By doing so, the power factor can be maintain to your required value and not to mentioned, it will save you lots of dollars as well as few more advantages by maintaining the power factor.

In this post, i don't want to write much on designing the capacitor bank. We go for basic, how capacitor bank look likes? Where to install? How the connection suppose to be?



These photos showing standard installation of Capacitor bank in MSB. One compartment of the switchboards panels are reserved for capacitor bank installation. The sizing/capacity of capacitor bank to be used and how many numbers are required will be covered in sizing capacitor bank.

Water Fountain Night Show

· 1 comments
These photos were taken during Testing and Commissioning of water fountain system in front of Sultan Abdul Halim Airport, kedah Malaysia. The lightings area arranged in such a way to synchronize with water shoot out from nozzle jet.






   


How to install water jet and lighting son that you can get the colorful water flying in the air? Check the photo below...

Installation Method for cable

· 8 comments
The followings are among the methods commonly adopted for cable installation. The choices of the method is depend on a few aspects such as drawing, space, constraint and materials available.


A1 - Insulated single core conductors in conduit in a thermally insulated wall

A2 - Multicore cable in conduit in a thermally insulated wall

This method also applies to single core or multicore cables installed directly in a thermally insulated wall (use methods A1 and A2 respectively), conductors installed in mouldings, architraves and window frames.



  • B1 - Insulated single core conductors in conduit on a wall
  • B2 - Multicore cable in conduit on a wall

This method applies when a conduit is installed inside a wall, against a wall or spaced less than 0.3 x D (overall diameter of the cable) from the wall. Method B also applies for cables installed in trunking / cable duct against a wall or suspended from a wall and cables installed in building cavities.


C - Single core or multi-core cable on a wooden wall

This method also applies to cables fixed directly to walls or ceilings, suspended from ceilings, installed on unperforated cable trays (run horizontally or vertically) and installed directly in a masonry wall (with thermal resistivity less than 2 K.m/W).




  • D1 - Multicore or single core cables installed in conduit buried in the ground
  • D2 - Multicore or single core cables buried directly in the ground










E - Multicore cable in free-air

This method applies to cables installed on cable ladder, perforated cable tray or cleats provided that the cable is spaced more than 0.3 x D (overall diameter of the cable) from the wall. Note that cables installed on unperforated cable trays are classified under Method C.




F - Single core cables touching in free-air

This method applies to cables installed on cable ladder, perforated cable tray or cleats provided that the cable is spaced more than 0.3 x D (overall diameter of the cable) from the wall. Note that cables installed on unperforated cable trays are classified under Method C.




G - Single-core cables laid flat and spaced in free-air

This method applies to cables installed on cable ladder, perforated cable tray or cleats provided that the cable is spaced more than 0.3 x D (overall diameter of the cable) from the wall and with at least 1 x D spacings between cables. Note that cables installed on unperforated cable trays are classified under Method C. This method also applies to cables installed in air supported by insulators.

Plumbing Works in Water Fountain

Tuesday, June 28, 2011 · 0 comments
Have you seen any piping installation work inside a pond/water fountain? This is one of the photo showing installation of HDPE pipe. There is 2 lines of HDPE pipes which provide water to 2 groups of nozzles.

Taxiway Edge Light

· 0 comments
This is Taxiway edge light (blue color). The main purpose of Taxiway light is to provide visual guide to pilot during taxing into parking apron.

The other 2 fittings in the photo is a taxiway centerline light and runway edge light of LED type.

Effects of Electrical Shocks According To Current

· 0 comments
Effects of the electric shocks

Listed below are the effects of electric shocks starting from the lowest amount of current flow to the highest for a duration of one second at typical household voltages.

1 mA - A normal person will feel a slight tingling sensation.

5 mA - A light shock will be felt, but most persons will be able to “let go”. Not a painful feeling, but definitely disturbing. However, a strong reflexive movement by the victim can cause further accidents and other type of injuries.

6 to 30 mA - The victim can be paralyzed, or the muscles will freeze (will not be able to release a tool, wire, or other object

Painful, and my not be possible to let go.

At high voltage (above 600 Volt, this current can already cause severe burns)

Women start to suffer the effect at lover current levels (6-26mA), while men can sustain until a bit higher (10 to 30 mA)

30 mA - Will cause respiratory paralysis
(The victim stops breathing for a period of time)

30 mA - This is the most sensitive rating of Earth Leakage Circuit Breakers (ELCB) normally installed in residential home in this country.

50 to 150 mA - The victim get an extremely painful shock.
The breathing stops (respiratory arrest).
Severe muscle contraction: flexor muscles may cause holding on, extensor muscles may cause intense pushing away.
Death is possible.

(At 75 mili-Ampere and above – The victim undergo ventricular fibrillation (very rapid, ineffective heartbeat). This condition can cause death within a few minutes. The only way to save the victim is by a special device called defibrillator.)

1 A and above - Uneven heartbeats occurs (Ventricular fibrillation).
The muscles will contract.
Damage to the nerves.
Death is likely.

4 A - The victim gets heart paralysis, which means the heart stops pumping.

(Highlight: How much is 4 amperes? If you connect a 1KW portable space heater to a wall socket outlet, and your house supply from the electricity company is 240 Volt, then that’s about 4.1 amperes running inside the wires from the socket to the space heater.)

5 A and above - Human tissues get burned.

10 A and above - Cardiac arrest and severe burns.
Death is probable.

Note: The above medical data has been obtained from the National
Institute for Occupational Safety and Health (NIOSH)

13 A - The lowest current a typical plug fuse will blow in a socket – plug supply connection.

15 A - Lowest level of current a normal circuit breaker or fuse will trip at a home distribution board, or a house electrical panel.

Further explanations on the electric shock injuries

The higher the current, the longer the time of the shock current, the more severe the injuries

(a) As you can see above, the higher the current that flow through a human body, and the longer it flows, the more serious the injuries.

If the shock is short in duration, it may only be painful. A longer shock (lasting a few seconds) could be fatal if the level of current is high enough to cause the heart to go into ventricular fibrillation.

100 mili-ampere current flow (that is one tenth of an ampere, or 0.1 Ampere) through the body will kill a person in just 2 seconds. Maybe he does not die immediately, but death is almost certain after sustaining 100 mA for 2 seconds.

(b) A person can only withstand less that 10 mili-amperes and still have control of his arm muscles. Beyond that, he no longer has control over his arms. That is the reason he cannot let go of the faulty tool he is holding (the hand may even tighten the grip on the electric tool), resulting in longer flow of shock current through the body thereby making the injuries more serious.

This situation when prolonged will lead to respiratory paralysis (the muscles that control breathing cannot move.)

That is part of the reason for the requirements to have install Earth Leakage Circuit Breakers (ELCB) for circuit supplying electrical tools. The ELCB can detect very small amount of leaked electrical current and trip that circuit within a fraction of a second thereby saving lives.

A severe shock can cause much more damage to the body than is visible. A person may suffer internal bleeding and destruction of tissues, nerves, and muscles.

Sometimes the hidden injuries caused by electrical shock result in a delayed death.
If a shock current is maintained long enough at a relatively high current, death is probably not avoidable.

But if somehow the contact area to the electrified object is broken fast enough and the victim’s heart has not yet been damaged, his normal heartbeat may return, even though this type of recovery is rare.

The severity of injuries depends on which part of the body does the shock current flow through

The most serious effect is when the current flow through the heart.

If a live wire accidentally touches the body by contact at the head, the nervous system will be severely damaged.

If during the accident the victim’s right hand touches the LIVE wire, while the left hand is holding the metal casing of the washing machine, the electrical current will flow through the chest. Then the lungs and heart will probably be injured.

Of course how severe will also depend of how many mili-amperes and how long the shock current flows.

If the current only flow through the arm portion, then the injuries can be as bad as the arm coming off while the victim still survive (not dead). There have been actual cases like these in high voltage accidents.

If the current does go through the chest, the person will almost surely be electrocuted.
A large number of serious electrical injuries involve current passing from the hands to the feet. Such a path involves both the heart and lungs.

This type of shock is often fatal.

A higher skin resistance will lower the shock current.

(a) Again the current is inversely proportional to the resistance. If the victim’s body is dry, then the shock current through his body will be lower. Then the injury will be less severe.

The resistance of a dry skin is can be 100,000 ohm or more. While that of a wet skin is only approximately 1,000 ohm.

At 600 volts, the dry skin resistance will only allow 6 mA at the most, while the wet skin can allow 600 mA to flow through the body.

Compare this to the list of injuries above and you can appreciate the extreme importance of dryness in the effort to avoid electrical shock.

Even at 240 volt, the wet skin will allow 240 mA to flow through the body, making very severe injuries and even death possible.

(b) Other than wet skin, wet working conditions will also have the same effect because they can make the skin wet and reduce resistance. Likewise, a damaged or broken skin.

(c) The resistance will also be reduced in direct proportion of the cross-sectional area of the path current. This means that when the contact made to an electrified object with an applied force as opposed to touching it with the tip of the fingers, the contact area will be larger. Therefore, the resistance to the current flow will be lower and the shock current will be higher.

Very Low Voltage also can kill

(a) The severity of the injury can increase the longer the victim is exposed to the shock current. Because of that, even low voltages can be extremely dangerous because the degree of injury depends not only on the amount of current but also on the length of time the body is in contact with the circuit.

Some victims have stopped breathing when shocked with currents from voltages as low as 49 volts.

For example, a shock current of 100 mA applied for 3 seconds can cause injuries as severe as a current of 900 mA applied for a fraction of a second.

(b) The victim’s muscle structure also plays a factor. People with less muscle tissue are typically affected at lower current levels.

The higher the voltage, the more serious the injuries.

(a) A current flow is directly proportional to the voltage supplying the current. That is why the higher the voltage, the higher the shock current flowing through the victim’s body. Therefore, the injuries will be more severe.

(b) At high voltage (i.e. 600 volts), the shock current can be as high as 4 amps. That amount of shock current will damage the hearts and other internal organs. In addition, internal blood vessels may clot, and the nerves in the area where the skin touches the electrified object may be damaged.

(c) High voltages can also cause severe tissue burns. A strong shock at the limb can cause the limb to come off.

Higher voltage can cause further accidents, therefore additional non-electrical injuries.

(a) Sometimes high voltages can lead to additional injuries. High voltages cause violent muscular contractions. The victim may lose his balance and fall, which can cause further injury or even death if he falls into machinery that can crush him.

(b) Bones can be fractured as a result from extreme muscle contractions during the shock, or cause by falling from working height.

Source: http://electricalinstallationwiringpicture.blogspot.com Electric shock injury pictures

Info

Saturday, June 4, 2011 · 0 comments
This blog is about electrical and mechanical installation works mainly on constructions related matters.

Total Pageviews

 

SKY DASHBOARD | Copyright © 2009 - Blogger Template Designed By BLOGGER DASHBOARD